Week 5
- The aim of week 5
- Procedure
All components related to this project have been connected together
and tested in this week.
Initially, the internal resistance of the previous inductor was far
bigger than the pure resistors in the load. This led that the phase difference
would be too small to be corrected. In this week, a transformer was utilized as an 7.5 mH inductor. Therefore, the measured power factor before the capacitor is 0.9106 which is displayed in the figure 1.
Figure 1. Measured Power Factor without Capacitors
In the next step, the value of the
capacitors was not large enough to correct the phase difference. Hence,
capacitors were changed to larger ones. Therefore, four 2.2mF compensation capacitors were utilized and connected into the circuit.
Finally, the program of
measuring the power factor and controlling the capacitors bank was tested to be
successful. Either the leading and lagging power factor can be measured and
displayed on the screen. The overall functionality of power factor correction
was accomplished.
The final circuit is shown in the figure 2.
The final circuit is shown in the figure 2.
Figure 2. Final circuit
The whole process was recorded in the video below.